Approvals/certifications Certified to EN54-2/4 by the LPCB (0832-CPD-0772).
Protocol/compatibility Apollo XP95/Discovery.
Mains supply 230V 50/60Hz.
Total output current limited to 3A @ 230Vac (Imax.A 270mA; Imin. 70mA).
Max battery size and type 2 x 12V 7Ah VRLA connected in series.
No. of loop drivers 2.
Max. loop output current 500mA (25V min; 34V max).
Max. addressable devices per loop 126.
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
Max. sounder output current 400mA.
Auxiliary relays 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
Expansion connections 2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm) 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finish Metal.
We are here to help.