Approvals/certifications Certified to EN54-2/4 by the LPCB (0832-CPD-0772). Protocol/compatibility Apollo XP95/Discovery. Mains supply 230V 50/60Hz. Total output current limited to 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA). Quiescent current 50mA (loop unloaded). Max battery size and type 2 x 12V 3.2Ah VRLA connected in series. No. of loop drivers 1. Max. loop output current 500mA (25V min; 34V max). Max. addressable devices per loop 126. No. of conventional sounder circuits 2 (Max. length per circuit is 500m). Max. sounder output current 400mA. Auxiliary relays 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc. Other outputs 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA. Auxiliary inputs 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching). Expansion connections 2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network). Product dimensions (mm) 380 W x 235 H x D 96mm Construction & finish Plastic lid and base; RAL7035 textured.